Thermostatic Expansion Valve

TA Series

thermostatic_expansion_valve_ta_series
Application

TA/TAE series are used to control liquid flow into evaporators of smaller capacities in refrigeration, heat pump, and air conditioning systems by sensing the refrigerant temperature at the evaporator outlet, where the bulb must be placed.

Features
  • Fixed and adjustable superheat, angleway and straightw
  • Available with strainer in inlet tube
  • Versions with and without external equalization, with and without bleed
  • Available with universal charge, range N or with MOP charge
Approvals

UL, CE

Technical Data
  • Applicable Refrigerants: R134a, R404A, R507, R290, and R407C
  • Max. Bulb Temperature: 120°C
  • Max. Valve Housing Temperature: 150°C
  • Max. Working Pressure: 3.4 MPa
  • Max. Test Pressure: 3.75 MPa
  • Equalization Connections: 6mm (1/4 in.) (solder ODF)
  • Capillary Tube Length: 750 mm (30 in.)
  • BP: 15% / 30%

TI Series

thermostatic_expansion_valve_ti_series
Application

TI/TIE series are used to  requlate liquid refrigerant flow injectiong into evaporator by sensing the refrigerant temperature at the evaporator outlet, where the sending bulb must be placed, and specially applied for refrigeration, ice machines applications, heat pumps as well as air conditioners

Features
  • Available with MOP
  • Interchangeable orifice assembly makes it easy to match capacity and storage
  • For bi-flow system, please contact us
Approvals

UL, CE

Technical Data
  • Applicable Refrigerants: R134a, R404A, R507, R407C, and R410A
  • Max. Temperature
    • Bulb when valve is installed: 100 °C
    • Bulb element not mounted: 60 °C
    • Valve body temperature: 100 °C
  • Max. Working Pressure: 4.6 MPa
  • Max. Test Pressure: 5.1 MPa
  • Pressure Equalization: 6mm (1/4”) (Solder ODF)
  • Capillay Tube Length: 1500mm

TCE/TCBE  Series

thermostatic_expansion_valve_tc_series
Application

TCE/TCBE  thermostatic expansion valves are used to adjust the supply of refrigerant in evaporator by controlling the superheat. The senor bulb is placed at the outlet of the evaporator. TCE/TCBE thermostatic expansion valves have been used in applications such as air conditioning system, heat pump, and chillers.

Features
  • Straight Way Design
  • Bleed Function
  • Bi-Flow Design; Balance Port Design
  • Adjustable Superheat
  • Available with MOP (MOP15°C)
  • Installation and various connections: Solder, Flare, MIO and ORFS
Approvals

UL, CE

Technical Data
  • Applicable Refrigerants: R134a,R404A,R507,R407C, and R410A
  • Max. Sensor Bulb Temperature: 100°C
  • Max. Valve Body Temperature: 110°C
  • Max. Working Pressure: 4.6 MPa
  • Max. Test Pressure: 5.1 MPa
  • External Balance Connection: 1/4 in. / 6 mm (ODF welding)
  • Capillary Lengths: 1500 mm
  • Bleed: 15%

TCCE Series

thermostatic_expansion_valve_tcce_series
Application

TCCE type thermostatic expansion valve is used to regulate refrigerant flow into the evaporator, especially in applications such as residential air conditioning systems, split systems, roof top units, heat pumps, light commercial air conditioning systems, and chillers.

Features
  • Compact size – hermetic design
  • Straight flow channel structure
  • Versions with and without check valve;
  • Product with BP function or special installation, please contact us
  • Connection possibilities: Solder and Chatleff
Approvals

UL, CE

Technical Data
  • Applicable Refrigerants: R407C, R410A, R134a, R404A, R507, R290, and R32
  • Max. Bulb Temperature: 100 °C
  • Max. Valve Body Temperature: 110°C
  • Max. Working Pressure: 4.6 MPa
  • Max. Test Pressure: 4.7 MPa
  • Options For Connections: ODF(3/8, 1/2, 5/8), ODM, etc.
  • Equalization:
    • 1/4 in. (ODF)
    • 1/8 in. (ODF/ODM)
  • Capillary Tube: 800 mm

Start typing and press Enter to search